TC40F

Antifreeze thermostat

application: antifreeze

operating mode: heating

Kod produktu: 1604

[d] Pliki do pobrania

Dane techniczne

Adjustment range:

-5°C...+15°C

Accuracy:

1°C

Hysteresis:

+/-0.8°C

Contact load capacity:

16(4)A 250V~

Pin arrangement:

SPDT switchable

Working conditions:

-10...60°C; 0...90%RH (non-condensing)

Installation:

surface-mounted or in a standard box, hole spacing 60mm

Electrical connections:

screw terminals, max. wire cross-section 4mm2

Degree and protection class:

IP20/II

  • Modern styling and high quality workmanship
  • Antifreeze thermostat

The antifreeze thermostat has a built-in double measuring bellows (measuring principle using the expansion of gases), thanks to which the measurement is stable and accurate. Thanks to the changeover contacts of the SPDT type, the thermostat can be used for cooling and heating. It is designed to control the operation of the boiler, zone valves, circulation pumps, electric heaters, fans, etc. It is equipped with an "on/off" switch and a signal lamp indicating the operation of the heating/cooling device. The knob has the function of limiting the temperature setting range (limiters every 1.5°C).