mounting: wall mounting range: -18°C... 15°C load capacity: 16A 250V operation: heating/cooling
Adjustment range: | -18°C...+15°C |
head type: | away |
Head dimensions (lxd): | 2000/6000x2mm |
Capillary length (L): | 2m or 6m |
Hysteresis: | 1.5°C |
Capillary material: | stainless steel |
Contact load capacity: | 16(4)A 250V~ |
Pin arrangement: | SPDT switchable |
Connectors: | bolted |
Housing dimensions: | 65x105x72mm |
Degree and protection class: | IP44 |
Antifreeze thermostats are used as protection against low temperatures in air-conditioning and ventilation systems. Reacts to temperature changes on any section of the capillary.The measurement is made along the entire length
The thermostat protects against damage due to freezing of heaters, filters and fans. The measuring element is a 2 or 6-meter capillary.
Typical applications
The contact of the antifreeze protection thermostat is switched when the temperature measured by the capillary drops below the value set with the knob. When the temperature rises above this value, the contact will automatically return to its initial position.
The entire length of the capillary is filled with gas, which under the influence of temperature changes its volume, causing the mechanism that changes the position of the working contact to operate. The capillary responds to temperature along its entire length.
© ESCO S.C 2024